|
December 2004 Issue No.11 |
Lead Story
|
EMSD Heightens Green Efforts
of
the Government Flying Service |
|
For
almost six years, EMSD's Airport Sector has been helping the Government
Flying Service (GFS) in energy conservation. The GFS has set a good
example on how a relatively small government unit can make great strides
in protecting the environment.
Since January 1999, the EMSD has been performing energy audits for the
GFS, particularly at their headquarters at Chek Lap Kok. As a result of
the improvement measures recommended and taken, the energy consumption
of the GFS has been significantly reduced since then, as measured in
terms of kilowatt-hours and costs. For instance, in 1999-2000, the GFS's
energy consumption was 5.43 million kilowatt-hours and the energy bill
amounted to $4.27 million. In 2003-04, the consumption was reduced by
21% to 4.28 million kilowatt-hours and the cost also dropped by 23% to
$3.29 million as illustrated in Figure 1.
Although the GFS headquarters is a relatively new building which was
commissioned in 1998, the EMSD was able to apply the latest technology
and identify a number of energy management opportunities (EMOs) for
further energy savings. EMOs are categorised into three levels, with Cat
1 needing only good housekeeping measures, Cat 2 requiring minor capital
investments, and Cat 3 calling for relatively major capital investments. |
|
Improvements |
|
The EMSD has helped the GFS to identify and implement
a number of EMOs. The following are just a few examples:
(a) Adjusting and monitoring the setting of the air-conditioning system
(Cat 1)
According to the actual requirements on temperature and relative
humidity in the GFS offices and workshops, adjustments were made and a
saving of 5% on the electricity bill (about $16,000 per month) was
recorded in August 1999 after the adjustment.
(b) Resetting the programmable lighting control (Cat 1)
The on/off time of the lighting at the car park and corridors in the
building was set according to the times of sunrise and sunset as advised
by the Hong Kong Observatory. This has led to a saving of around $3,000
a month in energy cost.
(c) Maintaining chiller operation at optimum level (Cat 1)
There are six chillers at the GFS headquarters. These chillers are
divided into two groups supplying chilled water to different parts of
the building under two control modes - day mode and night mode. Under the
day mode, the two groups of chillers operate independently. At night,
when the heat load is much lower, the chiller operation will be switched
to the night mode. The by-pass valve linking the two groups of chillers
will be opened so that one group of chiller can provide sufficient
chilled water and thus cool air for the whole building. Because of the
above reason and the reduction in demand for air-conditioning at night,
only one chiller is required during night mode.
During winter, the chiller system will be operated in night mode round
the clock. This has resulted in the reduction of monthly electricity
cost of around $20,000 during the winter months.
(d) Replacement of electro-magnetic ballasts by electronic ballasts (Cat
2)
All electro-magnetic ballasts used for the fluorescent lamps at the GFS
headquarters were replaced with electronic ballasts in 2001, resulting
in a saving of $11,000 per month in electricity cost.
(e) Using CO detectors to control the fresh air units (Cat 3)
With the assistance of the EMSD, the GFS has installed a CO-based
Demand Controlled Ventilation (DCV) System at their headquarters. This
system modulates outside air ventilation based on real-time occupancy as
detected by CO sensors installed inside the rooms. As the fresh air
intake is modulated, the heat gain is reduced. This reduces the loading
of chiller and minimises the power consumption of fresh air intake fan.
It is estimated that the system can cut the electricity bill by $161,000
per year. |
|
|
Figure 1 :
Energy Consumption of the GFS |
|
|
Green Task Force set up |
|
In February 2003, the
EMSD provided technical support to the GFS when they set up a Green Task
Force to introduce and implement energy saving measures. As a result,
the GFS has successfully implemented measures such as raising the room
temperature range of the workshops to 20-22 degrees and the aircraft
components store to 24-26 degrees etc. Through these measures, the GFS
reduced the expenditure on electricity by 8.1% or over $276,000 from
February to December 2003, compared with the corresponding period in
2002. |
|
|
Green
housekeeping |
|
The green housekeeping measures implemented in 2003 can be grouped into:
|
fixing the minimum settings of the thermostats |
|
reducing the consumption of paper and electricity |
|
using environmental friendly stationery, office equipment and lighting |
|
collecting recyclable materials |
|
implementing a smoke-free workplace policy |
|
conducting regular indoor air quality checks, and |
|
encouraging staff to contribute ideas on green practices. |
|
|
Experience to share |
|
The EMSD has had a very fruitful experience in
working with the GFS. The efforts made have contributed to significant
cost savings and, directly and indirectly, to a greener environment.
The GFS is only one example of how EMSD's consultancy service can
benefit other government departments and non-government clients. The
EMSD is always ready to share its accumulated experience with other
parties for the good of our Mother Earth. If you are interested in how
we can help save energy consumption in your organisation, please contact
our Business Support Manager Mr. L S Lai at 2808 3804. |
|
|